N2XSEBY 12/20 KV
CU/XLPE/CTS/PVC/STA/PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, Galvanized Steel Tape Armor, PVC Sheathed)
Standard Specification : SNI IEC 60502-2 : 2009
Application:
For installation indoor, in ground direct burried,
for power station and switchgear, if there is a
risk that low mechanical damage may occur.
Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
Note:
Conductor Shape
35 - 800 sqmm supplied in compacted circular stranded (cm) conductor shape
Electrical Data
Nom. Cross Section Area | Overall Diameter | Cable Weight | Conductor | Inductance
| Current-Carrying Capacity at 30oC | Short circuit current at 1 sec | |||
---|---|---|---|---|---|---|---|---|---|
DC Resistance at 20oC | AC Resistance at 90oC | ||||||||
approx. | approx. | Max. | Max. | in air | in ground | Conductor | Screen | ||
Max. | Max. | Max. | Max. | ||||||
(mm2) | (mm) | (kg/km) | (Ω/km) | (Ω/km) | (mH/km) | (A) | (A) | (kA) | (kA) |
3x35 | 56.5 | 4240 | 0.524 | 0.668 | 0.395 | 190 | 174 | 5.01 | 1.03 |
3x50 | 59.0 | 4792 | 0.387 | 0.494 | 0.379 | 226 | 205 | 7.15 | 1.03 |
3x70 | 63.0 | 5730 | 0.268 | 0.342 | 0.357 | 280 | 250 | 10.01 | 1.03 |
3x95 | 66.5 | 6785 | 0.193 | 0.247 | 0.341 | 338 | 298 | 13.59 | 1.37 |
3x120 | 70.0 | 7772 | 0.153 | 0.196 | 0.328 | 387 | 338 | 17.16 | 1.37 |
3x150 | 74.0 | 8945 | 0.124 | 0.159 | 0.318 | 437 | 378 | 21.45 | 1.37 |
3x185 | 77.5 | 10318 | 0.0991 | 0.128 | 0.308 | 497 | 426 | 26.46 | 1.37 |
3x240 | 84.5 | 13256 | 0.0754 | 0.098 | 0.296 | 580 | 488 | 34.32 | 1.37 |
3x300 | 89.5 | 15497 | 0.0601 | 0.079 | 0.287 | 655 | 545 | 42.90 | 1.37 |